Many products for you to choose from
G1013 HART to Foundation Fieldbus Converter
G1013 HART To Foundation Fieldbus converter designed by Microcyber Corporation is a gateway device for HART protocol and FF protocol. As HART master, G1013 HART to FF Gateway communicates with HART slave via HART interface, it can convert dynamic variables in the device to FF device variables output.
G1013 HART to Foundation Fieldbus Converter:
1.HART protocol to FF protocol
2.Support HART 7.0 protocol and backward compatible
3.Support up to 4 HART slave devices
4.Support 4 AI and 1 PID function block
Product Description
G1013 HART To Foundation Fieldbus converter designed by Microcyber Corporation is a gateway device for HART protocol and FF protocol. As HART master, G1013 HART to FF Gateway communicates with HART slave via HART interface, it can convert dynamic variables in the device to FF device variables output.
Outline dimension drawing of G1013 HART to Foundation Fieldbus converter:
Unit: mm
Structure diagram of G1013 HART to Foundation Fieldbus converter :
1 | Upside Housing | 2 | Bottom Housing | 3 | FF Communication Board |
4 | HART Bottom Board | 5 | Terminal |
Schematic diagram of G1013 HART to Foundation Fieldbus converter :
Detailed data list of G1013 HART to Foundation Fieldbus converter:
Basic parameters:
Measurement Object | HART slave device |
HART Power | 24VDC |
FF Bus Power | 9~32VDC |
Bus Protocol | 2-wire, FF Protocol |
Isolation Voltage | HART and FF bus interface, 500VAC |
Temperature Range | -40℃~85℃ |
Humility Range | 5~95%RH |
Start Time | ≤5s |
Refresh Time | 0.2s |
Performance:
Protection Level | IP20 |
EMC | GB/T 18268.1-2010 GB/T 18268.23-2010 |