NCS-TT106-R1 Smart Temperature Transmitter
NCS-TT106-R1 fieldbus temperature transmitter, using the fieldbus technology, is a new generation ofsmart fieldbus temperature transmitter and it is an indispensable field device for process control.
NCS-TT106-R1 Smart Temperature Transmitter:
1. Support 4 types of thermal resistance and 8 types of thermocouple
2. Thermal resistance supports 2-wire, 3-wire and 4-wire
3. The cold junction compensation accuracy of voltage signal can reach ±0.15 ℃
4. High precision (better than grade 0.1), low temperature drift (better than ±50ppm/℃)
5. NCS-TT106 FF: FCG interoperability test certification (ITK 6)
6. NCS-TT106 PA: PNO interoperability test certification (PA 3.02)
7. NCS-TT106 HART: CE, intrinsically safe, explosion-proof certification
Product Description
NCS-TT106-R1 series intelligent temperature transmitter: using the fieldbus technology, is a new generation of smart fieldbus temperature transmitter and it is an indispensable field device for process control. NCS-TT106H-R1 integrates abundant function blocks and realizes not only general measurement function but also complicated control strategy.
Outline dimension drawing of intelligent temperature transmitter:
Dimensional drawing (unit: mm)
Smart temperature transmitter wiring diagram:
Temperature transmitter wiring diagram
NCS-TT106-R1 adopts digital technology, which can be applied to various thermal resistance and thermocouple sensors. It has a wide measuring range, simple interface between the field and the control room, and can greatly reduce the cost of installation, operation and maintenance.
NCS-TT106-R1 series temperature transmitters support HART, FF, PA protocols, and can be widely used in petroleum, chemical, electric power, metallurgy and other industries.
NCS-TT106-R1 intelligent temperature transmitter thermal resistance technical indicators:
RTD room temperature accuracy index (25°C)
Signal type | Recommended scope (℃) | Accuracy(25℃) | Temperature drift(/℃) |
Resistor | 0 ~ 500Ω | ±0.04Ω | ±0.001Ω |
0 ~ 4000Ω | ±0.35Ω | ±0.015Ω | |
PT100 | -200 ~ 850℃ | ±0.15℃ | ±0.003℃ |
PT1000 | -200 ~ 850℃ | ±0.15℃ | ±0.005℃ |
Cu50 | -50 ~ 150℃ | ±0.15℃ | ±0.005℃ |
Cu100 | -50 ~ 150℃ | ±0.10℃ | ±0.003℃ |
NCS-TT106-R1 Intelligent Temperature Transmitter Thermocouple Specifications:
Thermocouple room temperature accuracy index:
Signal type | Recommended scope(℃) | Accuracy(25℃) | Temperature drift(/℃) |
Millivolt | -100 ~ +100mV | ±0.025mV | ±0.001mV |
B | 500 ~ 1810℃ | ±0.77℃ | ±0.050℃ |
E | -200 ~ 1000℃ | ±0.20℃ | ±0.025℃ |
J | -190 ~ 1200℃ | ±0.35℃ | ±0.01℃ |
K | -200 ~ 1372℃ | ±0.40℃ | ±0.025℃ |
N | -190 ~ 1300℃ | ±0.50℃ | ±0.015℃ |
R | 0 ~ 1768℃ | ±0.75℃ | ±0.023℃ |
S | 0 ~ 1768℃ | ±0.70℃ | ±0.023℃ |
T | -200 ~ 400℃ | ±0.35℃ | ±0.015℃ |
NCS-TT106-R1 intelligent temperature transmitter detailed data list:
Input signal | Pt100、Pt1000、CU50、CU100、0~500Ω、0~4000Ω B,E,J,N,K,R,S,T eight kinds of Thermocouple -100mV~100mV voltage signal |
Channel | Single |
RTD wiring | 2-wire, 3-wire, 4-wire |
Bus power | HART: 11~35 VDC |
Bus signal | HART,current mode |
Electric isolation | 1000VAC |
Working Temperature | -40℃~85℃ |
Humidity Range | 5%~95%RH |
Start Time | ≤5s |
Refresh Time | 0.5s |
EMC | GB/T 18268.1-2010 |
Protection | Terminal IP00, housing IP20 |
Voltage effect | ±0.005%/V |
Alarm signal | Alarm output can be set as 3.5…23 mA Upper/lower limit current 20.8mA / 3.8mA |
Current accuracy | 0.03% |